Twist-On Connector Range Guide
How to read the wire combination chart on a twist-on wire connector package, and what to check before using a connector for a splice.
Draft, open for review. Check every value against the governing standard and the manufacturer’s data before use.
What it is
Twist-on wire connectors (often called wire nuts) join two or more conductors by twisting a coiled spring or threaded insert onto the stripped ends. Each connector size is listed under UL 486C for specific combinations of wire sizes and counts. Those combinations are printed on the package or in the manufacturer's literature. There is no single industry chart. The combinations allowed for one brand and color do not apply to another brand, even if the colors match.
How to read it
Find the connector's combination chart. Each line lists a set of conductors that the connector is listed to join, such as two 12 AWG with one 14 AWG. Find the line that matches your exact splice, including the number of conductors, each size, and whether each is solid or stranded. If your combination is not on the chart, that connector is not listed for it.
What the chart shows
| Chart item | What it tells you | What to check |
|---|---|---|
| Wire size range | Smallest and largest wire the connector takes | Your splice must fall inside it |
| Combination lines | Exact sets of conductors the connector is listed for | Count and size of every conductor |
| Solid or stranded | Whether stranded or fixture wire is allowed | Mixed solid and stranded may need a specific line |
| Minimum and maximum conductors | How few and how many wires one connector can hold | Do not exceed the maximum |
| Voltage rating | Maximum system voltage | Must meet the circuit voltage |
| Temperature rating | Maximum operating temperature | Must suit the location, such as inside a luminaire |
| Conductor material | Copper only, or listed for aluminum and copper | Aluminum needs a connector specifically listed for it |
| Strip length | How much insulation to remove | Too long leaves bare copper exposed |
Key points
- Color identifies size only within one manufacturer's line. Read the package, not the color.
- Pre-twisting conductors is allowed by some makers and not needed by others; follow the instructions.
- A good splice has no bare conductor showing below the skirt, and each conductor holds when tugged.
- Wet and direct-burial locations need connectors listed for those conditions.
Common mistakes
- Using a connector for a combination not on its chart, such as one more wire than allowed.
- Joining aluminum and copper with a standard connector.
- Assuming one brand's red connector has the same range as another brand's red connector.
Governing standards: UL 486C (splicing wire connectors); NEC 110.14 (electrical connections). Manufacturer's combination chart and instructions govern.
Reference only. Verify against the current governing code or standard, the manufacturer's data and the project documents before use. Apps for Distributors disclaims liability arising from reliance on this reference.
More in Wall Charts
- Wire Gauge (AWG) Size & Dimension ChartAWG and kcmil sizes with solid-conductor diameters and cross-sectional areasRef EL-0048
- Electrical Wire Color CodesCode-required identification for grounded and grounding conductors, common conventions for ungrounded conductors, and international colorsRef EL-0049
- Common Electrical Symbols ChartOne-line and schematic symbols used on drawingsRef EL-0060
- Electrical Formulas Wall ChartOhm's law, power and single- and three-phase current formulasRef EL-0063