PVF Reference Library · Technical Reference

Galvanized Pipe and Fittings

Galvanized pipe is steel pipe coated with zinc to slow rust. It was once standard for water lines and is now used mostly for outdoor, structural, fence and some fire protection and air work. This sheet covers identification, where it fits and its limits.

Ref PV-0014ASTM A53ASME B16.3

Draft, open for review. Check every value against the governing standard and the manufacturer’s data before use.

What it is

Galvanized pipe is carbon steel pipe, usually ASTM A53, that has been hot-dip coated with zinc inside and out. The zinc corrodes first and protects the steel. Fittings are galvanized malleable iron to ASME B16.3 or galvanized cast iron to ASME B16.4, joined by tapered pipe threads. Sizes and wall thicknesses follow the same NPS and schedule system as black steel pipe. See the master guide to pipe sizes, schedules and wall thickness.

How to identify

Galvanized pipe has a dull gray to silver surface, sometimes with a crystal-like spangle. Black pipe is dark and oily. The stencil shows the standard (A53), grade, size, schedule and "GALV" or similar. Fittings are gray with a zinc finish and a raised cast marking. A magnet sticks to galvanized steel, which helps tell it from aluminum or stainless.

Where it is and is not used

UseTypical statusNotes
Fence posts, handrails, structural framesCommonOutdoor corrosion resistance
Dry-pipe and preaction fire sprinklerUsed where specifiedFollow NFPA 13 and the project spec
Outdoor and non-potable waterUsed in some areasCorrosion and scale build up over time
Compressed airUsed in some shopsZinc flakes can clog tools and filters
New potable water linesRare in new workCopper, PEX and CPVC replaced it in most codes
Natural gasRestricted by many utilities and codesUse black steel or other approved pipe unless allowed
Welding without precautionsNot acceptableZinc fumes cause metal fume fever

Key points

  • Threading and cutting remove the zinc. Bare threads rust first. Use a zinc-rich paint on cut ends where allowed.
  • Joining galvanized steel to copper causes galvanic corrosion. Use a dielectric union or fitting.
  • Old galvanized water lines often restrict flow from internal rust and scale and can release lead from old service connections. Inspect before reusing.
  • Welding or torch-cutting galvanized steel needs ventilation and fume control. Remove the zinc at the joint where practical.
  • Use NPT threads and a thread sealant rated for the service. See the NPT thread chart.

Common mistakes

  • Using galvanized pipe for a gas line where the code or utility forbids it.
  • Connecting galvanized steel straight to copper.
  • Mixing black and galvanized fittings in one system.
  • Welding galvanized steel in a closed space.

Governing standards: ASTM A53 (steel pipe, black and hot-dipped zinc-coated); ASME B16.3 (malleable iron threaded fittings); ASME B16.4 (gray iron threaded fittings). Local plumbing, fuel gas and fire codes.

Reference only. Verify against the current governing code or standard, the manufacturer's data and the project documents before use. Apps for Distributors disclaims liability arising from reliance on this reference.

Suggest an edit

This library is written in the open, like a wiki: anyone can suggest a correction or an addition, and each change is checked against the source before it goes live.

Know this subject well? Volunteer to review or write sheets.

← All PVF sheets

Your catalog, your prices and your name, on every customer’s phone.

Same app, same scanner, works with your existing ERP. Loaded with your catalog and your logo.