Communications and Data Cable (Cat 5e, 6, 6A)
Category cable is four-pair twisted copper data cable rated by bandwidth and performance under TIA-568. This sheet compares Cat 5e, 6 and 6A, explains CM, CMR and CMP listings and covers shielded vs unshielded cable.
Draft, open for review. Check every value against the governing standard and the manufacturer’s data before use.
What it is
Category cable carries Ethernet, PoE and other low-voltage signals over four twisted pairs. TIA-568 sets the performance for each category. The fire listing printed on the jacket (CMP, CMR and others) comes from UL 444 testing and the NEC communications articles and tells where the cable may be installed.
How to identify
Read the jacket print: category, conductor size (often 23 or 24 AWG), listing such as CMR or CMP, shielding (U/UTP, F/UTP, S/FTP), the maker and a footage mark. Cat 6 and 6A often have a plastic spline (cross filler) between the pairs. Shielded cable has a foil and a drain wire.
Category and listing comparison
| Item | Cat 5e | Cat 6 | Cat 6A |
|---|---|---|---|
| Rated bandwidth | 100 MHz | 250 MHz | 500 MHz |
| Typical use | 1 Gb Ethernet | 1 Gb; 10 Gb on short runs | 10 Gb Ethernet to full channel length |
| Max channel length (Ethernet) | 100 m | 100 m (10 Gb shorter) | 100 m |
| Listing | Where it is used | Can substitute for |
|---|---|---|
| CMP | Plenum spaces used for air handling | CMR, CMG, CM, CMX |
| CMR | Risers between floors | CMG, CM, CMX |
| CMG or CM | General building use, not riser or plenum | CMX |
| CMX | Limited use, such as dwellings | None |
Key points
- The 100 m channel is 90 m of permanent link plus up to 10 m of patch cords.
- Use connectors, jacks and patch panels rated for the same category. One lower-rated part lowers the whole link.
- Shielded cable must be bonded through shielded jacks and panels to work. An unbonded shield can make noise worse.
- PoE heats cable bundles. Larger bundles and higher PoE power may need derating per the cable maker and the NEC.
- Solid conductors are for horizontal runs. Stranded cable is for patch cords.
- Recent NEC editions moved communications cable rules into Articles 800 and 805. Check the edition in force.
Common mistakes
- Running CMR cable in a plenum ceiling.
- Untwisting pairs too far back at a termination.
- Using stranded patch cable for long horizontal runs.
- Mixing Cat 5e jacks with Cat 6A cable and expecting 6A results.
Governing standards: TIA-568 (cabling performance); UL 444 (communications cable); NEC Article 800 series (communications circuits).
Reference only. Verify against the current governing code or standard, the manufacturer's data and the project documents before use. Apps for Distributors disclaims liability arising from reliance on this reference.
More in Technical Reference
- Master Guide to Building Wire TypesTHHN/THWN-2, XHHW-2, RHW-2, USE-2 and other building wire types, how the letter codes decode and where each is usedRef EL-0001
- Breaker Types & Ratings ExplainedMiniature, molded-case, insulated-case and power breakers, GFCI/AFCI, supplementary protectors and what each nameplate rating meansRef EL-0002 · Safety-critical
- Nonmetallic-Sheathed Cable (NM-B)Construction, conductor count, jacket colors by size as an industry convention, and permitted and prohibited usesRef EL-0006
- Underground Feeder Cable (UF-B)Solid-jacket direct-burial cable, how it differs from NM-B and where it is usedRef EL-0007
- Service Entrance Cable (SE, SER, SEU, USE-2)Service and feeder cable styles, aluminum vs copper, and how SER differs from SEURef EL-0008
- Metal-Clad (MC) and Armored (AC) CableInterlocked armor cable types, grounding paths, MC-AP and health-care variantsRef EL-0009