Electrical Reference Library · Technical Reference

Communications and Data Cable (Cat 5e, 6, 6A)

Category cable is four-pair twisted copper data cable rated by bandwidth and performance under TIA-568. This sheet compares Cat 5e, 6 and 6A, explains CM, CMR and CMP listings and covers shielded vs unshielded cable.

Ref EL-0017NEC 800TIA-568UL 444

Draft, open for review. Check every value against the governing standard and the manufacturer’s data before use.

What it is

Category cable carries Ethernet, PoE and other low-voltage signals over four twisted pairs. TIA-568 sets the performance for each category. The fire listing printed on the jacket (CMP, CMR and others) comes from UL 444 testing and the NEC communications articles and tells where the cable may be installed.

How to identify

Read the jacket print: category, conductor size (often 23 or 24 AWG), listing such as CMR or CMP, shielding (U/UTP, F/UTP, S/FTP), the maker and a footage mark. Cat 6 and 6A often have a plastic spline (cross filler) between the pairs. Shielded cable has a foil and a drain wire.

Category and listing comparison

ItemCat 5eCat 6Cat 6A
Rated bandwidth100 MHz250 MHz500 MHz
Typical use1 Gb Ethernet1 Gb; 10 Gb on short runs10 Gb Ethernet to full channel length
Max channel length (Ethernet)100 m100 m (10 Gb shorter)100 m
ListingWhere it is usedCan substitute for
CMPPlenum spaces used for air handlingCMR, CMG, CM, CMX
CMRRisers between floorsCMG, CM, CMX
CMG or CMGeneral building use, not riser or plenumCMX
CMXLimited use, such as dwellingsNone

Key points

  • The 100 m channel is 90 m of permanent link plus up to 10 m of patch cords.
  • Use connectors, jacks and patch panels rated for the same category. One lower-rated part lowers the whole link.
  • Shielded cable must be bonded through shielded jacks and panels to work. An unbonded shield can make noise worse.
  • PoE heats cable bundles. Larger bundles and higher PoE power may need derating per the cable maker and the NEC.
  • Solid conductors are for horizontal runs. Stranded cable is for patch cords.
  • Recent NEC editions moved communications cable rules into Articles 800 and 805. Check the edition in force.

Common mistakes

  • Running CMR cable in a plenum ceiling.
  • Untwisting pairs too far back at a termination.
  • Using stranded patch cable for long horizontal runs.
  • Mixing Cat 5e jacks with Cat 6A cable and expecting 6A results.

Governing standards: TIA-568 (cabling performance); UL 444 (communications cable); NEC Article 800 series (communications circuits).

Reference only. Verify against the current governing code or standard, the manufacturer's data and the project documents before use. Apps for Distributors disclaims liability arising from reliance on this reference.

Suggest an edit

This library is written in the open, like a wiki: anyone can suggest a correction or an addition, and each change is checked against the source before it goes live.

Know this subject well? Volunteer to review or write sheets.