Underground Feeder Cable (UF-B)
UF-B is a jacketed cable rated for direct burial and wet locations. Its conductors are molded into a solid jacket, which is the main visible difference from NM-B.
Draft, open for review. Check every value against the governing standard and the manufacturer’s data before use.
What it is
Type UF-B (underground feeder and branch-circuit cable) is a factory assembly of insulated copper conductors and a bare equipment grounding conductor, all molded into a solid, moisture-resistant PVC jacket. It is listed to UL 493 and installed under NEC Article 340. It is used for runs to outbuildings, landscape lighting, wells, pumps and other outdoor or buried circuits.
How to identify
UF-B jackets are usually gray. The jacket is solid, so the conductors are embedded in it and are hard to separate. NM-B has a paper wrap and loose conductors inside a thin jacket. The print reads "UF-B," the size and conductor count (for example 12/2 with ground), the voltage, and often "sunlight resistant" and "for direct burial."
UF-B compared with NM-B
| Feature | NM-B | UF-B |
|---|---|---|
| Jacket | Thin PVC over paper-wrapped conductors | Solid PVC molded around conductors |
| Typical jacket color | White, yellow, orange, black by size | Gray |
| Wet and damp locations | Not permitted | Permitted |
| Direct burial | Not permitted | Permitted, at the depths in NEC 300.5 |
| Interior wiring | Permitted under Article 334 | Permitted, installed to the NM rules of Article 334 |
| Stripping | Easy | Harder; the jacket must be split away from each conductor |
| Governing article | NEC 334 | NEC 340 |
Key points
- Burial depth depends on the wiring method, location and circuit. The minimum cover table is NEC 300.5. Do not quote depths from memory.
- Where the cable comes out of the ground, NEC 300.5 also requires protection from physical damage, typically in conduit up to the box or equipment.
- NEC 340.12 lists places UF is not permitted, including as service-entrance cable and embedded in poured concrete except as allowed for heating cables.
- Exposure to sunlight is allowed only if the jacket is marked sunlight resistant.
- Ampacity is governed by NEC 340.80 and the code tables, not by the jacket rating.
Common mistakes
- Using NM-B outdoors or in buried conduit because it was on hand.
- Running UF-B out of the ground with no protection.
- Damaging conductor insulation while stripping the solid jacket with a knife.
- Assuming UF-B can serve as a service entrance. It cannot.
Governing standards: NEC Article 340; NEC 300.5 (underground installations); UL 493 (thermoplastic-insulated underground feeder and branch-circuit cables).
Reference only. Verify against the current governing code or standard, the manufacturer's data and the project documents before use. Apps for Distributors disclaims liability arising from reliance on this reference.
More in Technical Reference
- Master Guide to Building Wire TypesTHHN/THWN-2, XHHW-2, RHW-2, USE-2 and other building wire types, how the letter codes decode and where each is usedRef EL-0001
- Breaker Types & Ratings ExplainedMiniature, molded-case, insulated-case and power breakers, GFCI/AFCI, supplementary protectors and what each nameplate rating meansRef EL-0002 · Safety-critical
- Nonmetallic-Sheathed Cable (NM-B)Construction, conductor count, jacket colors by size as an industry convention, and permitted and prohibited usesRef EL-0006
- Service Entrance Cable (SE, SER, SEU, USE-2)Service and feeder cable styles, aluminum vs copper, and how SER differs from SEURef EL-0008
- Metal-Clad (MC) and Armored (AC) CableInterlocked armor cable types, grounding paths, MC-AP and health-care variantsRef EL-0009
- Tray Cable (TC and TC-ER)Multiconductor tray cable, exposed-run (ER) rating and industrial usesRef EL-0010