Electrical Reference Library · Technical Reference

Tray Cable (TC and TC-ER)

Tray cable (Type TC) is a factory-assembled multiconductor cable with an overall jacket, built for cable tray and other industrial raceway uses. This sheet explains the TC and TC-ER markings, common constructions and where each may be used.

Ref EL-0010NEC 336UL 1277

Draft, open for review. Check every value against the governing standard and the manufacturer’s data before use.

What it is

Type TC is power and control tray cable covered by NEC Article 336 and listed to UL 1277. It has two or more insulated conductors under a nonmetallic jacket, with or without a grounding conductor. It is used in cable tray, raceways and outdoor locations supported by messenger, and in other places Article 336 permits. TC-ER (exposed run) cable has passed added crush and impact tests. That lets it leave the tray and run exposed to equipment under the conditions in 336.10, usually in industrial establishments where only qualified persons service the installation.

How to identify

Read the print legend on the jacket. It shows the type letters, conductor count and size, insulation type, voltage rating and any added ratings such as sunlight resistant or direct burial. Power tray cable usually has a few larger conductors plus a ground. Control tray cable has many small conductors, often color coded by an ICEA method or printed with numbers. Check the legend and spec sheet for the color code.

Jacket marking decoder

MarkingMeaningNotes
TCTray cableBase type under NEC 336 and UL 1277
TC-ERTray cable, exposed runPassed crush and impact tests; exposed runs limited by 336.10
TC-ER-JPExposed run, joist pullAdded testing for pulling through framing where 336.10 permits
TC-ER-HLExposed run, hazardous locationsFor hazardous location uses where Chapter 5 permits
Sunlight resistantJacket is UV ratedNeeded for outdoor exposed runs
Direct burialRated for burial without racewayMust be marked; check burial rules in Article 300
LSLimited smokeOptional rating for certain spaces
ShieldedOverall or pair shieldsCommon on instrument and VFD cable

Key points

  • The conductor insulation type, such as THHN/THWN-2 or XHHW-2, sets the conductor ratings. Read it from the legend.
  • Ampacity comes from NEC 336.80 and the referenced tables. Do not estimate it.
  • Without the ER marking, TC cable must stay in tray, raceway or other supported methods Article 336 allows.
  • VFD tray cable is a special construction with symmetrical grounds and shields. It is not just TC with a different color.
  • Many TC cables are also listed as other types. Read the whole legend before quoting uses.

Common mistakes

  • Running plain TC exposed from the tray to a motor.
  • Ordering control cable by conductor count without confirming the color code method.
  • Using indoor-only cable for an outdoor exposed run.
  • Treating the jacket rating as permission to use the cable as building wire in dwellings.

Governing standards: NEC Article 336 (power and control tray cable); UL 1277 (electrical power and control tray cables). The adopted NEC edition and the cable spec sheet.

Reference only. Verify against the current governing code or standard, the manufacturer's data and the project documents before use. Apps for Distributors disclaims liability arising from reliance on this reference.

Suggest an edit

This library is written in the open, like a wiki: anyone can suggest a correction or an addition, and each change is checked against the source before it goes live.

Know this subject well? Volunteer to review or write sheets.

← All Electrical sheets

Your catalog, your prices and your name, on every customer’s phone.

Same app, same scanner, works with your existing ERP. Loaded with your catalog and your logo.