Copper Conductor Stranding Classes
Copper conductors come solid or stranded in classes that range from a few coarse strands to hundreds of fine ones. This sheet explains the common classes, where each is used and why fine-strand wire needs terminals identified for it.
Draft, open for review. Check every value against the governing standard and the manufacturer’s data before use.
What it is
Stranding class tells how many strands make up a conductor of a given size. More, finer strands make a more flexible conductor with the same copper area. ASTM B8 covers concentric-lay stranded conductors (Classes AA, A, B, C and D). ASTM B174 covers bunch-stranded conductors with very fine wires, used in flexible cords and welding cable. NEC Chapter 9, Table 10 lists the strand counts for Class B and Class C building wire.
How to identify
Building wire such as THHN and XHHW is normally Class B. Flexible cords, welding cable, DLO and some portable power cable use fine stranding, often described as Class K or Class M. Cable print may show the class; otherwise check the maker's spec sheet. Fine-strand wire feels very limp and the strands look like hair at a cut end.
Common classes
| Class | Construction | Typical use |
|---|---|---|
| Solid | One wire | Small branch-circuit wire, NM-B, control wiring |
| B | Concentric; 7 strands in 2 AWG and smaller, 19 in 1 to 4/0, 37 in 250 to 500 kcmil | Standard building wire |
| C | Concentric; more strands than Class B | Building wire where more flexibility is wanted |
| D | Concentric; more strands than Class C | Special flexible conductors |
| K | Bunch-stranded with 30 AWG strands | Flexible cord, portable cable |
| M | Bunch-stranded with 34 AWG strands | Welding cable, DLO, very flexible cable |
Key points
- NEC 110.14 requires connectors and terminals for conductors more finely stranded than Class B and Class C to be identified for that conductor class.
- Many standard mechanical lugs are listed only for Class B and C. Fine strands can splay out, cut, or creep from under a screw, causing heat.
- For fine-strand conductors, use lugs and crimp connectors marked for the class, or approved ferrules where the device allows.
- Class does not change the conductor size. A 4/0 Class M has about the same copper area as a 4/0 Class B, but a larger outside diameter.
- Fine-strand cable insulation may differ from building wire insulation. Check that the cable type is allowed for the use.
Common mistakes
- Landing welding cable or DLO in a standard set-screw lug.
- Tinning fine-strand ends with solder before clamping under a screw. Solder creeps and loosens.
- Choosing a conduit or lug size by gauge alone and finding the fine-strand cable does not fit.
Governing standards: ASTM B8 (concentric-lay stranded); ASTM B174 (bunch-stranded); NEC 110.14 and Chapter 9, Table 10; UL 486A-486B (wire connectors).
Reference only. Verify against the current governing code or standard, the manufacturer's data and the project documents before use. Apps for Distributors disclaims liability arising from reliance on this reference.
More in Technical Reference
- Master Guide to Building Wire TypesTHHN/THWN-2, XHHW-2, RHW-2, USE-2 and other building wire types, how the letter codes decode and where each is usedRef EL-0001
- Breaker Types & Ratings ExplainedMiniature, molded-case, insulated-case and power breakers, GFCI/AFCI, supplementary protectors and what each nameplate rating meansRef EL-0002 · Safety-critical
- Nonmetallic-Sheathed Cable (NM-B)Construction, conductor count, jacket colors by size as an industry convention, and permitted and prohibited usesRef EL-0006
- Underground Feeder Cable (UF-B)Solid-jacket direct-burial cable, how it differs from NM-B and where it is usedRef EL-0007
- Service Entrance Cable (SE, SER, SEU, USE-2)Service and feeder cable styles, aluminum vs copper, and how SER differs from SEURef EL-0008
- Metal-Clad (MC) and Armored (AC) CableInterlocked armor cable types, grounding paths, MC-AP and health-care variantsRef EL-0009