Electrical Metallic Tubing (EMT)
EMT is thin-wall, unthreaded steel or aluminum raceway joined with set-screw or compression fittings. It is the most common conduit for exposed and concealed branch circuits indoors.
Draft, open for review. Check every value against the governing standard and the manufacturer’s data before use.
What it is
Electrical metallic tubing (EMT) is a thin-wall metal raceway. It is too thin to thread, so it is joined with couplings and connectors that grip the outside of the tube. Most EMT is galvanized steel. Aluminum and stainless versions are also made. EMT is covered by NEC Article 358, listed to UL 797 and made to the dimensions in ANSI C80.3. It is sold by trade size, and the NEC limits its use to trade sizes 1/2 through 4.
How to identify
EMT has a smooth, bright or galvanized finish and no threads on the ends. Each 10 ft length is marked with the maker, trade size and listing. It is clearly lighter and thinner than rigid or IMC. Some EMT has a colored finish (red, blue and others) used to tell systems apart; color is not a rating. See the how to identify conduit types sheet.
Fitting types
| Fitting type | How it grips | Typical use | Notes |
|---|---|---|---|
| Set-screw | Screw bites the tube | Dry, indoor locations | Most common and lowest cost |
| Compression | Nut squeezes a ring onto the tube | Wet locations when listed raintight | Check the raintight marking |
| Concrete-tight | Set-screw or compression listed for concrete | Embedded in concrete | Must be marked concrete-tight |
| Indenter | Tool crimps tube and fitting | Older and specialty work | Less common today |
| Transition fittings | Adapt EMT to rigid, flex or boxes | Changes of raceway type | Use listed combination fittings |
Key points
- EMT is not threaded. Use fittings listed for EMT.
- Supports and securing intervals, bend limits and permitted locations are in Article 358. Bends between pull points may not total more than 360°.
- Listed EMT and fittings can serve as an equipment grounding conductor under NEC 250.118, if the fittings are made up tight. Many specs still call for a separate wire grounding conductor.
- Wet locations need fittings listed for wet locations. Outdoors, compression fittings are typical.
- Corrosion protection matters in soil, concrete slabs on grade and severe environments. Check 358.10 and the maker's guidance.
- Conductor fill is from NEC Chapter 9 tables. See the conduit trade size chart.
Common mistakes
- Using indoor set-screw fittings outdoors or in wet locations.
- Loose set screws that break the grounding path.
- Using EMT where severe physical damage is expected, where heavier raceway is required.
- Mixing EMT and rigid fittings without a listed transition.
Governing standards: NEC Article 358 (EMT); NEC 250.118 (grounding); UL 797 (EMT, steel); ANSI C80.3 (steel EMT dimensions); UL 514B (fittings).
Reference only. Verify against the current governing code or standard, the manufacturer's data and the project documents before use. Apps for Distributors disclaims liability arising from reliance on this reference.
More in Technical Reference
- Master Guide to Building Wire TypesTHHN/THWN-2, XHHW-2, RHW-2, USE-2 and other building wire types, how the letter codes decode and where each is usedRef EL-0001
- Breaker Types & Ratings ExplainedMiniature, molded-case, insulated-case and power breakers, GFCI/AFCI, supplementary protectors and what each nameplate rating meansRef EL-0002 · Safety-critical
- Nonmetallic-Sheathed Cable (NM-B)Construction, conductor count, jacket colors by size as an industry convention, and permitted and prohibited usesRef EL-0006
- Underground Feeder Cable (UF-B)Solid-jacket direct-burial cable, how it differs from NM-B and where it is usedRef EL-0007
- Service Entrance Cable (SE, SER, SEU, USE-2)Service and feeder cable styles, aluminum vs copper, and how SER differs from SEURef EL-0008
- Metal-Clad (MC) and Armored (AC) CableInterlocked armor cable types, grounding paths, MC-AP and health-care variantsRef EL-0009