Flexible Conduit (FMC, LFMC, LFNC)

Flexible conduit is used for short connections to motors, equipment and fixtures. FMC is bare metal, LFMC adds a liquidtight jacket over metal, and LFNC is all plastic, and each has limits on use as a grounding path.

Ref EL-0023NEC 348NEC 350NEC 356UL 1UL 360UL 1660

Draft, open for review. Check every value against the governing standard and the manufacturer’s data before use.

What it is

Flexible conduit bends by hand and absorbs vibration. There are three common types:

  • Flexible metal conduit (FMC): a spiral-wound metal strip with no jacket. NEC Article 348. Often called "Greenfield".
  • Liquidtight flexible metal conduit (LFMC): FMC with a PVC jacket that keeps out liquids. NEC Article 350.
  • Liquidtight flexible nonmetallic conduit (LFNC): plastic conduit with no metal core. NEC Article 356. It comes in types LFNC-A, LFNC-B and LFNC-C.

How to identify

FMC shows bare interlocked metal. LFMC looks like FMC covered in a smooth or ribbed jacket, usually gray or black, and you can feel the metal core. LFNC is lighter and has no metal core; it may be smooth or corrugated. The jacket print shows the type, trade size and listing.

Types compared

FeatureFMCLFMCLFNC
NEC article348350356
ConstructionBare metal spiralMetal core with PVC jacketNonmetallic, no metal core
Wet locationsNoYes, with liquidtight fittingsYes, with liquidtight fittings
Product standardUL 1UL 360UL 1660
Grounding pathLimited, see 250.118Limited, see 250.118Never, pull a ground wire
Typical useDry fixture and equipment whipsMotors, outdoor equipment, wash areasWet or corrosive areas, light duty

Grounding limitations

FMC and LFMC can count as an equipment grounding conductor only within strict conditions in NEC 250.118. These include a maximum total length in the ground return path, the trade size, the overcurrent device rating and whether flexibility is needed after installation. When any condition is not met, or flexibility is needed for vibration or movement, a separate equipment grounding conductor must be installed. LFNC is never a grounding path.

Key points

  • Use fittings listed for the conduit type. Liquidtight fittings are needed for LFMC and LFNC to stay liquidtight.
  • Securing, support and length limits for each type are in its NEC article.
  • Flexible conduit is usually limited to short runs where flexibility is needed, not long feeders.
  • Sunlight resistance and oil resistance are separate markings. Check the jacket print.

Common mistakes

  • Relying on flex as the only ground on a vibrating motor connection.
  • Using FMC in a wet location.
  • Using indoor straight connectors on liquidtight conduit.
  • Treating LFNC like metal flex for grounding.

Governing standards: NEC Articles 348, 350 and 356; NEC 250.118; UL 1 (FMC); UL 360 (LFMC); UL 1660 (LFNC); UL 514B (fittings).

Reference only. Verify against the current governing code or standard, the manufacturer's data and the project documents before use. Apps for Distributors disclaims liability arising from reliance on this reference.

Suggest an edit

This library is written in the open, like a wiki: anyone can suggest a correction or an addition, and each change is checked against the source before it goes live.

Know this subject well? Volunteer to review or write sheets.

← All Electrical sheets

Your catalog, your prices and your name, on every customer’s phone.

Same app, same scanner, works with your existing ERP. Loaded with your catalog and your logo.