Rigid Metal Conduit (RMC) and Intermediate Metal Conduit (IMC)
RMC and IMC are heavy-wall threaded metal conduits used where strength and physical protection matter. IMC has a thinner wall and lighter weight but uses the same threads and fittings as steel RMC.
Draft, open for review. Check every value against the governing standard and the manufacturer’s data before use.
What it is
Rigid metal conduit (RMC) is the heaviest metal raceway. It is made of galvanized steel, aluminum, stainless steel or red brass, and joined with threaded couplings. Intermediate metal conduit (IMC) is a steel conduit with a thinner wall than steel RMC. Its outside diameter is close enough that it takes the same threaded fittings. RMC is covered by NEC Article 344 and IMC by Article 342.
How to identify
Both come in 10 ft lengths with a coupling on one end and thread protectors on the other. Lengths are marked with the type, trade size and maker. Steel RMC is heavier than IMC in the same trade size. IMC is usually marked "IMC". Aluminum RMC is much lighter and non-magnetic. Stainless is bright and usually specified for corrosive or food areas.
RMC vs IMC
| Feature | RMC | IMC |
|---|---|---|
| NEC article | 344 | 342 |
| Materials | Steel, aluminum, stainless, red brass | Steel |
| Wall | Heaviest | Thinner than steel RMC |
| Trade sizes permitted | 1/2 through 6 | 1/2 through 4 |
| Threads | Tapered conduit thread | Same as RMC |
| Product standards | UL 6 (steel), UL 6A (aluminum, stainless, brass); ANSI C80.1 (steel), C80.5 (aluminum) | UL 1242; ANSI C80.6 |
Key points
- Conduit threads use the same 3/4 in per foot taper as pipe threads. Field threads must be cut with conduit dies and protected after cutting.
- Running threads are not allowed as couplings. Use a three-piece union or listed coupling where pieces cannot be turned.
- Support and securing intervals are in 344.30 and 342.30. The longer spans for straight runs are in Table 344.30(B)(2). Use the table, not a general rule.
- Dissimilar metals cause corrosion. Avoid direct contact of aluminum conduit with steel fittings in wet areas, and follow code for aluminum in concrete.
- RMC and IMC are listed as equipment grounding conductors under 250.118 when joints are tight.
- Conductor fill uses the RMC or IMC rows in NEC Chapter 9, Table 4. IMC has a slightly larger inside diameter than steel RMC.
Common mistakes
- Leaving freshly cut threads unprotected outdoors.
- Using EMT fittings on rigid or IMC.
- Assuming IMC is allowed in sizes above 4.
- Using aluminum conduit in concrete without the protection the code calls for.
Governing standards: NEC Articles 344 and 342; NEC 250.118; UL 6, UL 6A, UL 1242; ANSI C80.1, C80.5 and C80.6. See the conduit trade size chart.
Reference only. Verify against the current governing code or standard, the manufacturer's data and the project documents before use. Apps for Distributors disclaims liability arising from reliance on this reference.
More in Technical Reference
- Master Guide to Building Wire TypesTHHN/THWN-2, XHHW-2, RHW-2, USE-2 and other building wire types, how the letter codes decode and where each is usedRef EL-0001
- Breaker Types & Ratings ExplainedMiniature, molded-case, insulated-case and power breakers, GFCI/AFCI, supplementary protectors and what each nameplate rating meansRef EL-0002 · Safety-critical
- Nonmetallic-Sheathed Cable (NM-B)Construction, conductor count, jacket colors by size as an industry convention, and permitted and prohibited usesRef EL-0006
- Underground Feeder Cable (UF-B)Solid-jacket direct-burial cable, how it differs from NM-B and where it is usedRef EL-0007
- Service Entrance Cable (SE, SER, SEU, USE-2)Service and feeder cable styles, aluminum vs copper, and how SER differs from SEURef EL-0008
- Metal-Clad (MC) and Armored (AC) CableInterlocked armor cable types, grounding paths, MC-AP and health-care variantsRef EL-0009