Master Guide to Refrigerants

The common HVAC/R refrigerants: their chemical class, ASHRAE 34 safety group, typical applications and the federal rules that control their sale and use. It gives no pressure-temperature values.

Ref HV-0080ASHRAE 3440 CFR 8240 CFR 84

Safety-critical sheet, not yet signed off by an expert reviewer. Use it to understand the topic, then take every value and decision from the governing standard, the manufacturer’s instructions and a qualified person.

What it is

A refrigerant is the working fluid that carries heat in a vapor-compression system. Refrigerants are named with an "R-" number under ASHRAE Standard 34. ASHRAE 34 also gives each one a safety group: a letter for toxicity (A = lower, B = higher) and a number for flammability (1 = no flame propagation, 2L = mildly flammable, 2 = flammable, 3 = highly flammable). Federal rules restrict who may buy refrigerants (40 CFR 82 Subpart F, Section 608) and which refrigerants new equipment may use (40 CFR 84, AIM Act technology transitions).

How to identify

  • Equipment nameplate: shows the refrigerant type and factory charge. This is the first source to check.
  • Container label: shows the R-number, safety group and hazard statements. Under AHRI Guideline N, containers are no longer color-coded by refrigerant, so identify by the label, never by cylinder color. Containers of flammable (A2L and A3) refrigerants carry a red marking, and some use different valve threads that need their own adapters.
  • Unknown system charge: use a refrigerant identifier (analyzer). Do not guess from pressures.

Common refrigerants

RefrigerantClassASHRAE 34 safety groupTypical applicationStatus note
R-22HCFCA1Legacy residential and commercial ACProduction ended; service from recovered or reclaimed supply
R-410AHFC blendA1Residential and light commercial AC and heat pumpsBeing phased out of new equipment under 40 CFR 84
R-32HFCA2LDuctless and new residential ACLower-GWP replacement
R-454BHFO/HFC blendA2LNew residential and light commercial ACLower-GWP replacement for R-410A
R-134aHFCA1Chillers, medium-temperature refrigeration, automotive (older)Restricted in many new uses
R-1234yfHFOA2LAutomotive ACLower-GWP mobile refrigerant
R-1234ze(E)HFOA2LChillers, some commercialLower-GWP
R-513AHFO/HFC blendA1R-134a alternative in chillers and refrigeration
R-404AHFC blendA1Low- and medium-temperature commercial refrigerationRestricted in many new uses
R-448A / R-449AHFO/HFC blendsA1R-404A retrofits and new refrigeration
R-290 (propane)HydrocarbonA3Self-contained commercial and domestic refrigerationHighly flammable; charge limits apply
R-744 (CO₂)NaturalA1Transcritical commercial refrigerationVery high operating pressures
R-717 (ammonia)NaturalB2LIndustrial refrigerationToxic; specialized handling

Key points

  • Do not mix refrigerants or "top off" a system with a different refrigerant. Use only refrigerants and procedures approved by the equipment manufacturer.
  • Zeotropic blends (400-series, such as R-410A, R-454B and R-448A) must be charged as liquid to avoid fractionation.
  • A2L refrigerants need A2L-rated equipment, tools, recovery machines and leak detectors, and installation per UL 60335-2-40 and ASHRAE 15.
  • Sales: under 40 CFR 82.154, refrigerant sales are generally restricted to Section 608 (or 609 for motor-vehicle AC) certified technicians, with recordkeeping under 40 CFR 82.166. Small-can and other exceptions are in the rule.
  • Pressure-temperature data comes from the refrigerant manufacturer. Blends have separate bubble and dew points.

Common mistakes

  • Identifying a cylinder by color.
  • Selling A1-only tools or recovery equipment for A2L work.
  • Recommending "drop-in" replacements without checking oil compatibility and the manufacturer's approval.

Governing standards: ASHRAE 34 (designation and safety classification); ASHRAE 15 (safety code); UL 60335-2-40; 40 CFR 82 Subpart F; 40 CFR 84; 49 CFR 172–180 for shipping and cylinders; AHRI 700 (purity); AHRI Guideline N (container marking).

Reference only. Verify against the current governing code or standard, the manufacturer's data and the project documents before use. Apps for Distributors disclaims liability arising from reliance on this reference.

Suggest an edit

This library is written in the open, like a wiki: anyone can suggest a correction or an addition, and each change is checked against the source before it goes live.

Know this subject well? Volunteer to review or write sheets.

← All HVAC sheets

Your catalog, your prices and your name, on every customer’s phone.

Same app, same scanner, works with your existing ERP. Loaded with your catalog and your logo.