Electrical Reference Library · Measure & Identify
How to Identify a NEMA Plug or Receptacle
NEMA plugs and receptacles are identified by a configuration code that sets voltage, current rating and pin layout. This sheet shows how to find the code on a device and how to identify an unmarked one by its blade shapes.
Draft, open for review. Check every value against the governing standard and the manufacturer’s data before use.
What it is
NEMA WD 6 defines the shape and spacing of plug blades and receptacle slots so that a plug fits only receptacles of the same rating. Each layout has a code, such as 5-15R or L14-30P. Straight-blade and locking devices have separate series. The full set of drawings is in the NEMA Receptacle Configuration Chart. For device types, see Receptacle Types and NEMA Configurations.
How to identify
- Read the face or back of the device. Most are marked with the NEMA code and ratings in amps and volts.
- If unmarked, note the blade style. Flat straight blades or curved locking blades.
- Count the blades and pins. Note any round or U-shaped ground pin.
- Note blade shapes and angles: parallel, tandem (in line), angled, T-shaped slot, or a bent blade.
- Match to the chart. Compare against the NEMA Receptacle Configuration Chart drawings.
Reading the code
| Part | Example | Meaning |
|---|---|---|
| L prefix | L14-30P | Locking (twist-lock) device; no prefix means straight blade |
| Number before the dash | 14 | Configuration family: voltage and wiring arrangement |
| Number after the dash | 30 | Current rating in amps |
| Suffix | P or R | P is a plug; R is a receptacle |
Common configurations
| Code family | Voltage | Arrangement |
|---|---|---|
| 1 | 125 V | 2-pole, 2-wire, no ground |
| 5 | 125 V | 2-pole, 3-wire grounding |
| 6 | 250 V | 2-pole, 3-wire grounding |
| 10 | 125/250 V | 3-pole, 3-wire, no ground (older dryer and range) |
| 14 | 125/250 V | 3-pole, 4-wire grounding |
| 15 | 250 V three-phase | 3-pole, 4-wire grounding |
Key points
- A 5-20R receptacle has a T-shaped slot and accepts both 5-15P and 5-20P plugs.
- Locking devices are not interchangeable with straight-blade devices of the same family.
- The rating on the device is the device rating. Circuit protection and wire size come from the NEC.
- Replacing a 10-series receptacle with a 14-series may require a new grounding conductor and cord. Follow the NEC.
- Industrial devices may also carry IEC 60309 pin-and-sleeve configurations, which are a separate system.
Common mistakes
- Reading the amp number as the configuration.
- Forcing an adapter between configurations.
- Mixing up P and R when ordering.
- Assuming two locking devices with the same amp rating fit each other.
Governing standards: NEMA WD 6 (wiring device configurations); NEC Article 406 (receptacles and attachment plugs); UL 498 (attachment plugs and receptacles).
Reference only. Verify against the current governing code or standard, the manufacturer's data and the project documents before use. Apps for Distributors disclaims liability arising from reliance on this reference.
More in Measure & Identify
- How to Identify Conduit TypesField identification of EMT, IMC, RMC, PVC, ENT and flexible conduits by wall, threads, markings and fittingsRef EL-0066
- How to Read a Building Wire Print LegendDecoding the surface printing on wire and cableRef EL-0067
- How to Measure Wire Gauge in the FieldUsing a wire gauge, calipers and stripping tool marks, and the stranded-wire trapRef EL-0068
- How to Identify Solid, Stranded and Compact ConductorsVisual identification and why it matters for terminationsRef EL-0069
- How to Measure Conduit Trade SizeWhy trade size is not the measured diameter and how to confirm itRef EL-0075
- How to Identify Conduit FittingsTelling set-screw, compression, threaded and liquidtight fittings apartRef EL-0076