How to Identify a NEMA Plug or Receptacle

NEMA plugs and receptacles are identified by a configuration code that sets voltage, current rating and pin layout. This sheet shows how to find the code on a device and how to identify an unmarked one by its blade shapes.

Ref EL-0074NEMA WD 6

Draft, open for review. Check every value against the governing standard and the manufacturer’s data before use.

What it is

NEMA WD 6 defines the shape and spacing of plug blades and receptacle slots so that a plug fits only receptacles of the same rating. Each layout has a code, such as 5-15R or L14-30P. Straight-blade and locking devices have separate series. The full set of drawings is in the NEMA Receptacle Configuration Chart. For device types, see Receptacle Types and NEMA Configurations.

How to identify

  1. Read the face or back of the device. Most are marked with the NEMA code and ratings in amps and volts.
  2. If unmarked, note the blade style. Flat straight blades or curved locking blades.
  3. Count the blades and pins. Note any round or U-shaped ground pin.
  4. Note blade shapes and angles: parallel, tandem (in line), angled, T-shaped slot, or a bent blade.
  5. Match to the chart. Compare against the NEMA Receptacle Configuration Chart drawings.

Reading the code

PartExampleMeaning
L prefixL14-30PLocking (twist-lock) device; no prefix means straight blade
Number before the dash14Configuration family: voltage and wiring arrangement
Number after the dash30Current rating in amps
SuffixP or RP is a plug; R is a receptacle

Common configurations

Code familyVoltageArrangement
1125 V2-pole, 2-wire, no ground
5125 V2-pole, 3-wire grounding
6250 V2-pole, 3-wire grounding
10125/250 V3-pole, 3-wire, no ground (older dryer and range)
14125/250 V3-pole, 4-wire grounding
15250 V three-phase3-pole, 4-wire grounding

Key points

  • A 5-20R receptacle has a T-shaped slot and accepts both 5-15P and 5-20P plugs.
  • Locking devices are not interchangeable with straight-blade devices of the same family.
  • The rating on the device is the device rating. Circuit protection and wire size come from the NEC.
  • Replacing a 10-series receptacle with a 14-series may require a new grounding conductor and cord. Follow the NEC.
  • Industrial devices may also carry IEC 60309 pin-and-sleeve configurations, which are a separate system.

Common mistakes

  • Reading the amp number as the configuration.
  • Forcing an adapter between configurations.
  • Mixing up P and R when ordering.
  • Assuming two locking devices with the same amp rating fit each other.

Governing standards: NEMA WD 6 (wiring device configurations); NEC Article 406 (receptacles and attachment plugs); UL 498 (attachment plugs and receptacles).

Reference only. Verify against the current governing code or standard, the manufacturer's data and the project documents before use. Apps for Distributors disclaims liability arising from reliance on this reference.

Suggest an edit

This library is written in the open, like a wiki: anyone can suggest a correction or an addition, and each change is checked against the source before it goes live.

Know this subject well? Volunteer to review or write sheets.

← All Electrical sheets

Your catalog, your prices and your name, on every customer’s phone.

Same app, same scanner, works with your existing ERP. Loaded with your catalog and your logo.