Electrical Reference Library · Measure & Identify

How to Measure Wire Gauge in the Field

Wire size can be checked in the field with a wire gauge, calipers or the stripping holes on a stripper. This sheet shows each method and the stranded-wire trap that leads to wrong sizes.

Ref EL-0068ASTM B258

Draft, open for review. Check every value against the governing standard and the manufacturer’s data before use.

What it is

Wire size is normally read from the print legend. When the print is gone, measure the bare conductor. AWG sizes follow a formula, so each size has a set diameter for solid wire. Stranded wire measures larger than solid of the same size, because of the gaps between strands. Full diameters are in the Wire Gauge (AWG) Size & Dimension Chart.

How to identify

  1. Try the legend first. Look along the run for a clean section of print.
  2. Strip a short length. Do not nick the conductor.
  3. Solid wire: use a wire gauge plate. Find the smallest slot the wire passes through without forcing. The slot is the size. Measure in the slot, not the round hole behind it.
  4. Or use calipers. Measure the bare conductor and compare with the chart.
  5. Stranded wire: count the strands and measure one strand, or measure the bundle lightly and compare with stranded diameters, not solid.
  6. Stripper check: the hole that strips cleanly without cutting strands is a good hint, not proof.

Methods

MethodGood forTrap
Print legendAll wireWorn or missing print
Wire gauge plateSolid wireDo not force; stranded wire reads wrong
Calipers on solid wireAny solid sizeCompare with solid diameters only
Calipers on stranded wireLarger stranded wireBundle reads larger than solid of the same size
Strand count plus one strandStranded wireNeed the stranding class; see Copper Conductor Stranding Classes
Stripper holesQuick checkStrippers vary; holes wear

Key points

  • The AWG diameter formula is d = 0.005 in × 92^((36 − n)/39), where n is the gauge. For 0000 use n = −3.
  • Every three gauge steps roughly halves the area. Every six steps roughly halves the diameter.
  • Compact stranded conductors are smaller than standard stranded of the same size. See How to Identify Solid, Stranded and Compact Conductors.
  • Insulation thickness varies by type. Never size wire by its outside diameter with insulation on.
  • When in doubt, treat the wire as the smaller size.

Common mistakes

  • Measuring stranded wire and reading the solid chart, so the wire looks one size bigger.
  • Measuring with the insulation on.
  • Forcing wire into a gauge slot.
  • Trusting a worn stripper.

Governing standards: ASTM B258 (AWG diameters); ASTM B8 (concentric-lay stranded conductors); NEC Chapter 9, Table 8 (conductor properties).

Reference only. Verify against the current governing code or standard, the manufacturer's data and the project documents before use. Apps for Distributors disclaims liability arising from reliance on this reference.

Suggest an edit

This library is written in the open, like a wiki: anyone can suggest a correction or an addition, and each change is checked against the source before it goes live.

Know this subject well? Volunteer to review or write sheets.

← All Electrical sheets