Electrical Reference Library · Measure & Identify
How to Identify Conduit Fittings
Conduit fittings join conduit to boxes and to other conduit. This sheet shows how to tell set-screw, compression, threaded and liquidtight fittings apart and what each is listed for.
Draft, open for review. Check every value against the governing standard and the manufacturer’s data before use.
What it is
Conduit fittings include connectors, which attach conduit to a box or enclosure, and couplings, which join two pieces of conduit. The fitting type must match the conduit type and the location: dry, damp, wet or embedded in concrete.
Listing marks on the fitting or carton show what the fitting may be used for, such as raintight, wet locations or concrete-tight.
How to identify
- Identify the conduit type. EMT, rigid, IMC, PVC and flexible conduit each use their own fittings. See How to Identify Conduit Types.
- Look at how it grips. A screw that presses on the conduit means set-screw. A nut that squeezes a ring around the conduit means compression. Pipe threads mean threaded. A nut, sealing ring and a ferrule that goes inside the conduit mean liquidtight.
- Read the trade size cast or stamped on the body.
- Read the carton for listing and location marks.
- Check the material. Steel and zinc die-cast are common. Malleable iron is used for heavy duty fittings.
Fitting identification table
| Fitting | Tells | Used with | Location notes |
|---|---|---|---|
| Set-screw | One or two screws press on conduit | EMT | Dry and damp; check carton for concrete-tight |
| Compression | Nut and gland ring squeeze the conduit | EMT | Raintight versions listed for wet locations |
| Threaded | Pipe threads, locknut and bushing | Rigid and IMC | Wet and hazardous locations with the right fitting |
| Threadless (rigid) | Compression or set-screw for unthreaded rigid | Rigid and IMC | Check listing |
| Squeeze (FMC) | Clamp squeezes the flex | FMC | Dry locations |
| Screw-in (FMC) | Threads into the convolutions | FMC | Dry locations |
| Liquidtight | Nut, sealing ring, ferrule | LFMC, LFNC | Wet locations when listed |
| PVC adapter | Solvent-weld socket with thread | PVC | Wet locations |
Key points
- Insulated throats or bushings protect conductors at the box entry.
- Steel and die-cast fittings may serve as part of the grounding path only when listed for it.
- Straight, 45 and 90 degree liquidtight connectors are common.
- See Conduit Fittings — Set-Screw, Compression and Threaded for more on each type.
Common mistakes
- Using set-screw EMT fittings outdoors.
- Mixing EMT fittings on rigid conduit.
- Leaving out the ferrule on liquidtight fittings.
- Over-tightening die-cast fittings until they crack.
Governing standards: NEMA FB 1 (fittings, cast metal boxes and conduit bodies); UL 514B (conduit, tubing and cable fittings); NEC articles for each conduit type.
Reference only. Verify against the current governing code or standard, the manufacturer's data and the project documents before use. Apps for Distributors disclaims liability arising from reliance on this reference.
More in Measure & Identify
- How to Identify Conduit TypesField identification of EMT, IMC, RMC, PVC, ENT and flexible conduits by wall, threads, markings and fittingsRef EL-0066
- How to Read a Building Wire Print LegendDecoding the surface printing on wire and cableRef EL-0067
- How to Measure Wire Gauge in the FieldUsing a wire gauge, calipers and stripping tool marks, and the stranded-wire trapRef EL-0068
- How to Identify Solid, Stranded and Compact ConductorsVisual identification and why it matters for terminationsRef EL-0069
- How to Identify a NEMA Plug or ReceptacleMatching blade shape, ground pin and locking style to a configurationRef EL-0074
- How to Measure Conduit Trade SizeWhy trade size is not the measured diameter and how to confirm itRef EL-0075