HVAC Reference Library · Wall Charts
Capacitor Identification Chart
How to tell run, dual-run and start capacitors apart by case style and terminals, and how to read the label fields that must match on a replacement.
Draft, open for review. Check every value against the governing standard and the manufacturer’s data before use.
What it is
HVAC motors and compressors use two kinds of capacitors. Run capacitors are metallized film units that stay in the circuit while the motor runs. Start capacitors are electrolytic units that are only in the circuit for a moment at start-up. A dual run capacitor combines two run capacitors in one can, usually one for the compressor and one for the outdoor fan. EIA-456-A covers metallized film motor run capacitors.
How to identify
- Case: Run capacitors usually have a metal can, round or oval. Start capacitors usually have a black plastic case, almost always round.
- Terminals: A single run capacitor has two terminals, often with several tabs each. A dual run capacitor has three: C (common), HERM (compressor) and FAN.
- Label: Read the full label before removing the old part. Take a photo.
- Discharge first. Capacitors can hold a charge after power is off. Discharge safely with a proper tool before handling.
Label fields chart
| Label field | What it means | Replacement rule |
|---|---|---|
| µF or MFD | Capacitance in microfarads | Match the rating. Dual units show two values, such as 45+5 |
| Tolerance (for example ±5% or ±6%) | Allowed spread from the rated µF | Use for testing; replacement tolerance should be equal or tighter |
| VAC | Rated AC voltage, such as 370 or 440 | Same or higher voltage rating |
| Hz | Rated frequency, usually 50/60 | Match the supply |
| Temperature range | Allowed operating temperature | Same or wider range |
| Protected or P-marking | Has an internal pressure-sensitive interrupter | Use a protected unit where the original was protected |
| HERM / FAN / C | Terminal functions on dual units | Connect each wire to the same terminal |
| Start capacitor range (for example 88–108 µF) | Start caps are rated as a range | Match the range and voltage |
Key points
- Never swap a start capacitor for a run capacitor, or the reverse. Electrolytic start capacitors are not built for continuous duty.
- A higher voltage rating is fine. A lower one is not.
- A bulging top or leaking case means the capacitor has failed. Check the motor or compressor too.
- Test with a meter that reads capacitance, with the capacitor out of the circuit and discharged.
Common mistakes
- Swapping HERM and FAN wires on a dual capacitor.
- Choosing a replacement by case size instead of µF and voltage.
- Handling a capacitor without discharging it.
Governing standards: EIA-456-A (metallized film motor run capacitors); UL 810 (capacitors); the equipment wiring diagram and the motor or compressor manufacturer's data.
Reference only. Verify against the current governing code or standard, the manufacturer's data and the project documents before use. Apps for Distributors disclaims liability arising from reliance on this reference.
More in Wall Charts
- Thermostat Wire Color CodesConventional terminal letters and the wire colors commonly used for eachRef HV-0042
- Refrigerant Safety Group Chart (A1, A2L, A3, B)Toxicity and flammability classes explainedRef HV-0043
- ACR Tube Size Chart (Actual OD vs Plumbing Nominal)Matching ACR OD sizes to plumbing nominal sizesRef HV-0045
- MERV Rating ChartMERV groups and what they captureRef HV-0047
- Nominal vs Actual Filter Size ChartWhy a nominal filter size differs from its actual dimensionsRef HV-0048
- HVAC Electrical Symbols ChartWiring diagram symbolsRef HV-0050