HVAC Electrical Symbols Chart
Plain-language descriptions of the symbols most often found on HVAC wiring and ladder diagrams. Symbols vary by maker, so the legend on the unit's diagram always governs.
Draft, open for review. Check every value against the governing standard and the manufacturer’s data before use.
What it is
HVAC wiring diagrams use graphic symbols for switches, coils, motors and other parts. Many are based on IEEE 315 (ANSI Y32.2), but each equipment maker adds its own. Most units carry two drawings: a connection (pictorial) diagram that shows where wires land, and a ladder (schematic) diagram that shows how the circuit works. This chart describes the common symbols in words.
How to read it
- Start with the legend on the unit's diagram. It defines the abbreviations (such as CC, IFR, LPS) and line types.
- Read the ladder diagram from the left rail (power) to the right rail (common), one rung at a time.
- Contacts are drawn in their de-energized or shelf state.
- Contacts that belong to a coil carry the same label as the coil.
Symbol chart
| Symbol (as drawn) | Meaning | Common labels |
|---|---|---|
| Two short parallel lines across the wire | Normally open (NO) contact | CC, R, IFR |
| Two parallel lines with a diagonal slash | Normally closed (NC) contact | CR, R |
| Circle with letters inside | Relay or contactor coil | CC, CR, IFR |
| Two coils side by side with a line between | Transformer | TRANS |
| Circle with M or a motor label | Motor | IFM, OFM, COMP |
| Two parallel lines, one curved | Capacitor | CAP, RC, SC |
| Zigzag line | Resistor or heater | HTR, CH |
| Small rectangle or S-curve in line | Fuse | FU |
| Switch blade with a diaphragm or bellows | Pressure switch | HPS, LPS |
| Switch blade with a wavy or thermal element | Temperature switch or overload | TS, OL, LS |
| Lines fanning down to a point | Ground | GND |
| Dashed line | Field wiring, or a mechanical link between parts (see legend) | — |
| Solid dot at a crossing | Wires connected | — |
Key points
- Field wiring vs factory wiring: Many makers draw factory wiring solid and field wiring dashed. Others use the opposite or a different color. Check the legend.
- A crossing with no dot usually means the wires cross without connecting.
- The same symbol can mean different parts on different brands. Use the parts list to confirm.
- Safety controls are usually drawn in series with the coil they protect.
Common mistakes
- Reading NC contacts as open because the unit is off.
- Assuming all dashed lines are field wiring.
- Using a symbol chart from one brand to troubleshoot another without reading its legend.
Governing standards: IEEE 315 (graphic symbols for electrical diagrams); the equipment manufacturer's wiring diagram and legend.
Reference only. Verify against the current governing code or standard, the manufacturer's data and the project documents before use. Apps for Distributors disclaims liability arising from reliance on this reference.
More in Wall Charts
- Thermostat Wire Color CodesConventional terminal letters and the wire colors commonly used for eachRef HV-0042
- Refrigerant Safety Group Chart (A1, A2L, A3, B)Toxicity and flammability classes explainedRef HV-0043
- ACR Tube Size Chart (Actual OD vs Plumbing Nominal)Matching ACR OD sizes to plumbing nominal sizesRef HV-0045
- Capacitor Identification ChartCase styles, terminals and label fieldsRef HV-0046
- MERV Rating ChartMERV groups and what they captureRef HV-0047
- Nominal vs Actual Filter Size ChartWhy a nominal filter size differs from its actual dimensionsRef HV-0048