HVAC Reference Library · Technical Reference

Compressors (Reciprocating, Scroll, Rotary, Screw)

HVAC compressors are grouped by how they compress gas: reciprocating, scroll, rotary and screw. This sheet covers each type, how to read a compressor nameplate and what must match when one is replaced.

Ref HV-0012UL 60335-2-34

Draft, open for review. Check every value against the governing standard and the manufacturer’s data before use.

What it is

The compressor raises the pressure and temperature of refrigerant vapor so the system can reject heat. Reciprocating compressors use pistons and valves. Scroll compressors use one fixed and one orbiting spiral. Rotary compressors use a rolling piston or vane in a cylinder. Screw compressors use one or two meshing rotors and are used on larger chillers. Each can be hermetic (sealed in a welded shell), semi-hermetic (bolted shell that can be opened) or open (motor outside the compressor). Capacity can be fixed speed, two-stage, digital or variable speed (inverter).

How to identify

Read the nameplate. It shows maker, model, serial, refrigerant, voltage and phase, rated load amps (RLA), locked rotor amps (LRA) and often the oil type. Shape helps too. Scroll compressors are tall cylinders. Rotary compressors in mini-splits and PTACs are smaller, with an external suction accumulator beside the shell. Semi-hermetic reciprocating compressors have bolted heads and cast bodies. Single-phase compressors have three terminals marked C, S and R.

Compressor types

TypeHow it compressesTypical equipmentNotes
Reciprocating, hermeticPistons in a sealed shellOlder residential, small commercial, refrigerationValves can fail; tolerates some liquid poorly
Reciprocating, semi-hermeticPistons, serviceable bolted bodyCommercial refrigeration, older chillersCan be rebuilt
ScrollOrbiting spiral against fixed spiralResidential and light commercial AC and heat pumpsFew moving parts; rotation direction matters on 3-phase
RotaryRolling piston or vaneMini-splits, PTACs, window unitsOften inverter driven
ScrewMeshing rotorsChillers and large refrigerationLarge oil separation systems

Key points

  • A replacement must match the refrigerant, oil type, voltage and phase, and capacity, and must be approved by the equipment or compressor maker.
  • Three-phase scroll compressors run backward if two legs are swapped. They are noisy and do not pump.
  • Inverter compressors are driven by a matched board. They are not run directly on line power.
  • After a compressor burnout, plan for an acid test, suction line drier and oil change. See filter driers.
  • RLA and LRA are for wiring and protection decisions by the installer. Overcurrent sizing comes from the nameplate and code, not the counter.

Common mistakes

  • Replacing a compressor without matching the oil type to the refrigerant.
  • Ignoring rotation on a three-phase scroll.
  • Swapping a fixed-speed compressor into an inverter system.
  • Skipping the start components check on single-phase units.

Governing standards: UL 60335-2-34 (safety of motor-compressors); equipment and compressor maker data.

Reference only. Verify against the current governing code or standard, the manufacturer's data and the project documents before use. Apps for Distributors disclaims liability arising from reliance on this reference.

Suggest an edit

This library is written in the open, like a wiki: anyone can suggest a correction or an addition, and each change is checked against the source before it goes live.

Know this subject well? Volunteer to review or write sheets.

← All HVAC sheets

Your catalog, your prices and your name, on every customer’s phone.

Same app, same scanner, works with your existing ERP. Loaded with your catalog and your logo.