Duct Sealants and Tapes

Duct closures must be listed for the duct they seal. UL 181A covers tapes and mastic for duct board, UL 181B covers tapes and mastic for flex duct, and ordinary cloth duct tape is not listed for either.

Ref HV-0023UL 181AUL 181B

Draft, open for review. Check every value against the governing standard and the manufacturer’s data before use.

What it is

Duct sealants close joints and seams so conditioned air stays in the duct. The two families are tapes (foil or film with adhesive) and mastics (thick paste brushed or troweled on, often with mesh in wide gaps). Codes require closures on duct board and flex duct to be listed to UL 181A or UL 181B. Sheet metal joints are usually sealed with mastic, listed tape or gaskets as the code and project specs call for.

How to identify

Listed tapes have the listing printed on the tape backing at regular intervals, such as "UL 181A-P" or "UL 181B-FX". Mastic containers show the listing on the label, such as "UL 181A-M" or "UL 181B-M". If the backing does not show a 181 marking, assume it is not listed.

Listing markings

MarkingProductUsed on
181A-PPressure-sensitive tapeFibrous glass duct board
181A-HHeat-activated tapeFibrous glass duct board
181A-MMasticFibrous glass duct board
181B-FXPressure-sensitive tapeFlexible air ducts and connectors
181B-CClamp (non-metallic band)Flexible air ducts and connectors
181B-MMasticFlexible air ducts and connectors

Key points

  • Match the marking to the duct type. A 181A tape is listed for duct board, not flex.
  • Clean, dry and dust-free surfaces are needed for tape to stick. Cold surfaces are a common cause of failed tape.
  • Heat-activated tape needs the right iron temperature and pressure to bond. Watch for the color change dot where used.
  • Mastic is often the more durable choice for sheet metal and for joints that will be hard to reach later.
  • Mesh tape embedded in mastic bridges wider gaps. Follow the maker's gap limits.
  • Many energy codes call for duct leakage testing. Good sealing is what makes the test pass.

Common mistakes

  • Using cloth duct tape on ducts. It dries out and lets go.
  • Taping flex duct inner liner without a clamp, or clamping without sealing.
  • Taping over dust or condensation.
  • Using a mastic not rated for the duct's operating temperature or for outdoor exposure where needed.

Governing standards: UL 181A (closure systems for rigid air ducts); UL 181B (closure systems for flexible air ducts and connectors); International Mechanical Code and energy code duct sealing provisions; SMACNA seal classes for sheet metal.

Reference only. Verify against the current governing code or standard, the manufacturer's data and the project documents before use. Apps for Distributors disclaims liability arising from reliance on this reference.

Suggest an edit

This library is written in the open, like a wiki: anyone can suggest a correction or an addition, and each change is checked against the source before it goes live.

Know this subject well? Volunteer to review or write sheets.

← All HVAC sheets

Your catalog, your prices and your name, on every customer’s phone.

Same app, same scanner, works with your existing ERP. Loaded with your catalog and your logo.