Registers, Grilles and Diffusers

Registers, grilles and diffusers are the air terminals at the end of the duct. A grille has no damper, a register adds a damper, and a diffuser spreads air in several directions, and each is selected from rated throw, noise and pressure drop data.

Ref HV-0024AHRI 880ASHRAE 70

Draft, open for review. Check every value against the governing standard and the manufacturer’s data before use.

What it is

Air terminals deliver supply air into a room or return it to the system. The main types are:

  • Grille: a face with fixed or adjustable bars and no damper. Common on returns.
  • Register: a grille with a built-in damper to adjust or shut off airflow. Common on supply in homes.
  • Diffuser: a supply outlet that spreads air in several directions, usually in a ceiling. Square, round, louvered, plaque and slot styles are common.
  • Linear slot diffuser: long narrow outlet used along windows and in modern ceilings.

How to identify

Look for a damper lever or blades behind the face. If present, it is a register. Ceiling outlets with cones or louvers that throw air sideways are diffusers. Sizes are given by the duct opening (the neck or wall opening), not the outer face, which is larger.

Terminal types and uses

TypeDamperAir patternTypical location
Return grilleNoInlet onlyWalls, ceilings, doors
Filter grilleNoInlet with filter slotReturn at air handler
Supply registerYesOne or two wayFloors, walls, low sidewall
Ceiling diffuserOptionalTwo to four way, or roundCommercial and residential ceilings
Linear slot diffuserOptionalOne or two way along lengthPerimeter and architectural ceilings
Floor registerYesUpwardUnder windows on older homes

Selection terms

  • Throw: the distance the air travels before slowing to a set terminal velocity. Too short leaves dead spots; too long causes drafts.
  • Noise criterion (NC): the rated sound level. Lower is quieter.
  • Pressure drop: the static pressure lost through the outlet at a given airflow.
  • Face velocity and neck velocity: higher velocity raises noise and throw.

These values come from the maker's catalog, tested to ASHRAE 70. AHRI 880 is the certification program for air terminals.

Key points

  • Size outlets from the airflow for each run, then check throw and NC in the maker's data.
  • A damper at the register is for fine balancing. Major balancing belongs at branch dampers.
  • Match the outlet pattern to the room. Ceiling diffusers near walls may need a blank-off on one side.
  • Return grilles need enough free area to keep noise and pressure drop down.

Common mistakes

  • Ordering by face size instead of duct opening size.
  • Using a register damper to fix a badly sized system.
  • Placing a high-throw outlet where it blows directly on people.
  • Ignoring free area on filter grilles.

Governing standards: ASHRAE 70 (method of testing air outlets and inlets); AHRI 880 (air terminals); maker's performance data.

Reference only. Verify against the current governing code or standard, the manufacturer's data and the project documents before use. Apps for Distributors disclaims liability arising from reliance on this reference.

Suggest an edit

This library is written in the open, like a wiki: anyone can suggest a correction or an addition, and each change is checked against the source before it goes live.

Know this subject well? Volunteer to review or write sheets.

← All HVAC sheets

Your catalog, your prices and your name, on every customer’s phone.

Same app, same scanner, works with your existing ERP. Loaded with your catalog and your logo.